A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Car light fixtures do not illuminate.
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Car lighting worked upon arrival. When lighting disconnect was turned off light fixtures didn't light possible bad light ballast,
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate inside the machine room
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate
|
3/27/2023
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate
|
3/17/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate
|
3/29/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency telephone not operational. Mandatory Re-inspetion due in 14 days. Alarm Bell works.
|
3/12/2025
|
A17.1-1996 : Elevators
|
2.37 Pressure switch
|
306.14 Pressure switch
|
x
|
|
Install low pressure switch on control valve. Cylinder head is above control valve.
|
3/27/2023
|
A17.1-1996 : Elevators
|
2.37 Pressure switch
|
306.14 Pressure switch
|
x
|
|
Install low pressure switch. Top of cylinder is above storage tank.
|
3/17/2022
|
A17.1-1996 : Elevators
|
2.37 - Pressure Switch
|
306.14
|
x
|
|
Need to install low pressure switch on control valve
|
3/29/2024
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
No state operating certificate on site. Need to display the certificate inside the machine room
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Pit light fixture does not illuminate. No lamp in fixture.
|
|
A17.1-1996 : Elevators
|
2.14 - Code data plate
|
215
|
|
|
Post code data plate on controller or disconnect
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
Post firefighter operating instructions next to hall fire keyswitch
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
Post firefighter operating instructions next to hall fire keyswitch
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
PROVIDE A WORKING IN CAR EMERGENCY PHONE
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Remove hydraulic oil from pit sump hole.
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Replace burnt-out car lighting.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State Operating Certificate has not been available since 5/07/2020.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(c)(2)
|
|
|
Test and log documentation of firefighter operation monthly.
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
The Phase I Operation Procedures shall be placed @ the Main Egress Location.
|
|
A17.1-1996 : Elevators
|
2.37 Pressure switch
|
306.14 Pressure switch
|
x
|
|
When the top of the cylinder head is above the top of the storage tank a switch shall be provided to be incompliance with A17.1 section 306.14.
|
3/12/2025
|