Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 3.16 - Traveling cables and junction boxes 1001.2(c)(22) The traveling cable is damaged under the car and shall be repaired or replaced. 7/2/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit light shall be operational. 7/2/2020
A17.1-1996 : Elevators 3.16 - Traveling cables and junction boxes 1001.2(c)(22) The traveling cable is damaged under the car and shall be repaired or replaced. 7/2/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit light shall be operational. 7/2/2020
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 4/6/2023
A17.1-1996 : Elevators 3.16 - Traveling cables and junction boxes 1001.2(c)(22) The traveling cable is damaged under the car and shall be repaired or replaced. 7/2/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit light shall be operational. 7/2/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/6/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. 4/6/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 4/6/2023
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. 4/6/2023
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d All machine rooms or enclosures shall have a self-locking door and shall be operable from the interior space without the use of a key. 4/6/2023
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) x x The suspension means shall be replaced. One belt is damaged/worn. Elevator Red Tagged. 6/21/2024
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 1001.2(b)(28) x The governor sheave has excessive wear. Per the manufacturer's specifications, the governor sheave shall be replaced within 30 days. 6/29/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Due to the condition of the governor sheave, the following category 5 testing items remain: governor pull-out/pull-thru, spinning of governor to calculate electrical and mechanical tripping speeds, car safeties shall be tested with full load at contract speed. 6/29/2022
A17.1-1996 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 1001.2(e)10 x The car safeties shall be tested. 5/18/2020
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The in car emergency lighting shall be operational. 4/7/2022
A17.1-1996 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 1001.2(e)10 x The car safeties shall be tested. 4/30/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x x The car alarm bell shall be operational. - Elevator Red-Tagged for not having a working notification system for emergency situations. 4/30/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x x The in car emergency telephone shall be operational. - Elevator Red-Tagged for not having a working notification system for emergency situations. 4/30/2020