A17.1-1996 : Elevators
|
5.6 - Governor-rope tension devices
|
206.7
|
|
|
2.18.7.2 - Governor tail sheave switch shall be repaired or replaced. (held together by electrical tape)
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
x
|
|
2.26.2.22 - Counterweight buffer gas spring-return switch is broken.
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be obtained and displayed in the machine room.
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3d
|
|
|
All machine rooms or enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Clean the car top.
|
|
A17.1-1996 : Elevators
|
2.11 - Disconnecting Means and Control
|
210.4
|
|
|
Disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device.
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
In car emergency telephone shall work with 24/7 support.
|
4/21/2020
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
Make the machine room lighting above the controller operational.
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
MCP fire service testing must be properly documented monthly on log sheet.
|
|
A17.1-1996 : Elevators
|
1.8 - Door closing force
|
1001.2(a)(8)
|
x
|
|
Provide and record the door closing force.
|
4/9/2019
|
A17.1-1996 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
1001.2(b)(28)
|
x
|
|
Provide category 1 testing of car governor.
|
4/9/2019
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide testing of emergency lights and bell.
|
4/9/2019
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)12
|
x
|
|
Provide testing of Phase 1 & Phase 2 fire service operation.
|
4/9/2019
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
Repair or re-lamp light directly above the controller.
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
Repair or re-lamp light directly above the controller. (Multi year violation)
|
|
A17.1-1996 : Elevators
|
3.28 - Counterweight and counterweight buffer
|
1001.2(c)(13)
|
x
|
|
Replace the counterweight roller guides where needed for proper operation.
|
5/18/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Replace the counterweight roller guides where needed for proper operation.
|
|
A17.1-1996 : Elevators
|
5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions
|
1001.2(e)10
|
x
|
|
The car safeties shall be tested.
|
5/18/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The counterweight rollers are making a lot of noise. Repair or replace the rollers as needed.
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
12/10/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
5/18/2020
|
A17.1-1996 : Elevators
|
3.16 - Traveling cables and junction boxes
|
1001.2(c)(22)
|
|
|
The traveling cable is damaged under the car and shall be repaired or replaced.
|
|
A17.1-1996 : Elevators
|
3.16 - Traveling cables and junction boxes
|
1001.2(c)(22)
|
|
|
The traveling cable is damaged under the car and shall be repaired or replaced.
|
|
A17.1-1996 : Elevators
|
1.12 - Car enclosure
|
204
|
|
|
Tighten/repair car interior handrail.
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
|
|