Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Replace unreadable in-car capacity plate.
A17.1-1996 : Elevators 1.12 - Car enclosure 1001.2(a)(12) There is an open hole in the car operating panel that shall be covered.
A17.1-1996 : Elevators 1.2 - Stop switches 210.2(e) x Repair or replace the faulty in-car stop switch. 9/11/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. The phone did not work at all with or without the 110v power. 12/27/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. The phone shall be operational on main and auxiliary power. 5/26/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational on main and auxiliary power, and give proper location of car. (2nd Notice) 9/11/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency telephone shall work. 5/24/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Packing was blown during the pressure test and elevator left out of service. The following testing items still need to be tested to finish annual inspection: Relief pressure test, 15 minute standing test, fire service, door pressure, ERU test, emergency phone, light, and alarm. 11/2/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x The elevator dropped significantly during the 15 minute standing test. Take corrective action as needed. The relief pressure test and 15 minute standing test will need to be witnessed again. Elevator Red Tagged 11/23/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) x The overspeed valve in not tagged or sealed. A category 5 test shall be performed and witnessed on the overspeed valve. 11/23/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) x The overspeed valve in not tagged or sealed. A category 5 test shall be performed and witnessed on the overspeed valve. 12/27/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The following items still need to be tested: (1) Door pressure, (2) Testing of emergency alarm, phone and light with 110v source removed, (3) Fire service, (4) Low pressure switch. 11/23/2022
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code The machine room lighting shall be operational.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting The machine room lighting shall be repaired. 1 or more bulbs are not working.
A17.1-1996 : Elevators 2.36 - Hydraulic Cylinders 1004.2(b)(19) x Car settled during standing test. Visible leakage at packing gland. Make necessary repairs to correct. 11/17/2020
A17.1-1996 : Elevators 2.4 - Machine space 101.1a Repair multiple large holes in the machine room ceiling.
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) All non elevator related items and materials shall be removed from the machine room.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit shall be kept clean. Clean the pit.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit light shall be operational.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit shall be kept clean and dry.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The oil recovery bucket is full.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 The pit shall be kept clean. Remove excess debris.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.