A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
All non elevator related items and materials shall be removed from the machine room.
|
|
A17.1-1996 : Elevators
|
2.36 - Hydraulic Cylinders
|
1004.2(b)(19)
|
|
x
|
Car settled during standing test. Visible leakage at packing gland. Make necessary repairs to correct.
|
11/17/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency telephone shall work.
|
5/24/2019
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Packing was blown during the pressure test and elevator left out of service. The following testing items still need to be tested to finish annual inspection: Relief pressure test, 15 minute standing test, fire service, door pressure, ERU test, emergency phone, light, and alarm.
|
11/2/2022
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
101.1a
|
|
|
Repair multiple large holes in the machine room ceiling.
|
|
A17.1-1996 : Elevators
|
1.2 - Stop switches
|
210.2(e)
|
x
|
|
Repair or replace the faulty in-car stop switch.
|
9/11/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Replace unreadable in-car capacity plate.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
x
|
The elevator dropped significantly during the 15 minute standing test. Take corrective action as needed. The relief pressure test and 15 minute standing test will need to be witnessed again. Elevator Red Tagged
|
11/23/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The following items still need to be tested: (1) Door pressure, (2) Testing of emergency alarm, phone and light with 110v source removed, (3) Fire service, (4) Low pressure switch.
|
11/23/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational on main and auxiliary power, and give proper location of car. (2nd Notice)
|
9/11/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational. The phone did not work at all with or without the 110v power.
|
12/27/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational. The phone shall be operational on main and auxiliary power.
|
5/26/2023
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
The machine room lighting shall be operational.
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
The machine room lighting shall be repaired. 1 or more bulbs are not working.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
The oil recovery bucket is full.
|
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspection)
|
x
|
|
The overspeed valve in not tagged or sealed. A category 5 test shall be performed and witnessed on the overspeed valve.
|
12/27/2022
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspection)
|
x
|
|
The overspeed valve in not tagged or sealed. A category 5 test shall be performed and witnessed on the overspeed valve.
|
11/23/2022
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
The pit light shall be operational.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
The pit shall be kept clean and dry.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
The pit shall be kept clean. Clean the pit.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
The pit shall be kept clean. Remove excess debris.
|
|
A17.1-1996 : Elevators
|
1.12 - Car enclosure
|
1001.2(a)(12)
|
|
|
There is an open hole in the car operating panel that shall be covered.
|
|