MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current certificate in machine room
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication inoperable. Re-inspection required
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
OSV is not sealed, perform required testing, seal & tag within 90 days. Re-inspection required
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)(12) -
|
|
|
The Phase 2 instructions in the cab are illegible.
|
6/3/2020
|
A17.1-1996 : Elevators
|
1.15 - sign and operating device symbols
|
1001.2(a)(15)
|
|
|
The inside of the cab shall be labeled as "Elevator #2".
|
12/3/2020
|
A17.1-1996 : Elevators
|
2.10 - Numbering of elevators, machines, and disconnect switches
|
1001.2(b)(10)
|
|
|
The first floor elevator entrance shall be labeled as "Elevator #2".
|
12/3/2020
|
A17.1-1996 : Elevators
|
1.12 - Car enclosure
|
1001.2(a)(12)
|
|
|
ADA handrail missing from elevator cab. Replace handrail.
|
12/3/2020
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
1001.2(b)(8)
|
|
|
The heat detector in the machine room shall be within 2' of the sprinkler head.
|
12/3/2020
|
A17.1-1996 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
1001.2(a)(16)
|
|
|
The capacity tag in the cab is illegible.
|
12/3/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work, suspect low line voltage, may need to be reprogrammed to new maintenance company number
|
7/20/2022
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV is not sealed and must have a cat 5 weight test performed within 90 days or less
|
7/20/2022
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV unsealed, provide testing.
|
7/24/2023
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide working emergency cars lights,bell was ok.
|
7/24/2023
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(b)
|
|
|
Provide current year documents for the MCP.
|
3/8/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
A written maintenance control program shall be kept on site for each elevator
|
3/8/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
overspeed valve not sealed. Must be cat 5 tested
|
6/20/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone line not working
|
6/20/2024
|