Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone shall work, suspect low line voltage, may need to be reprogrammed to new maintenance company number 7/20/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone line not working 6/20/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency communication inoperable. Re-inspection required
A17.1-1996 : Elevators 1.12 - Car enclosure 1001.2(a)(12) ADA handrail missing from elevator cab. Replace handrail. 12/3/2020
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) The inside of the cab shall be labeled as "Elevator #2". 12/3/2020
A17.1-1996 : Elevators 1.16 - Rated load, platform area, and data plate 1001.2(a)(16) The capacity tag in the cab is illegible. 12/3/2020
A17.1-1996 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 1001.2(b)(10) The first floor elevator entrance shall be labeled as "Elevator #2". 12/3/2020
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 1001.2(b)(8) The heat detector in the machine room shall be within 2' of the sprinkler head. 12/3/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) - The Phase 2 instructions in the cab are illegible. 6/3/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Provide working emergency cars lights,bell was ok. 7/24/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current certificate in machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A written maintenance control program shall be kept on site for each elevator 3/8/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(b) Provide current year documents for the MCP. 3/8/2024
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed and must have a cat 5 weight test performed within 90 days or less 7/20/2022
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV unsealed, provide testing. 7/24/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x overspeed valve not sealed. Must be cat 5 tested 6/20/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x OSV is not sealed, perform required testing, seal & tag within 90 days. Re-inspection required