Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone failed 11/8/2018
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.8 Switch Keys Fire Service Phase I Key must be removable in the on position. 211.8
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.8 Switch Keys Must make Fire Service Phase I Key switch bezel with key possition indications readable. 211.8
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Must replace Jack packing gland to limit oil loss. 8.6.5.5.1