Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 1/12/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 1/12/2026
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No An ABC type fire extinguisher with a current test tag shall be mounted convenient to the machine room door. 1/12/2026
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No The pit light shall be operational. 1/12/2026
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) No No The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. 1/12/2026
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 1001.2(c)(18) No No The load weigher control system in the overhead shall have the cover installed. 1/12/2026
MO Minimum : Elevators (I) - Pits (I)8 No No Pit sump holes, with or without pumps, and well holes that are accessible, shall be covered flush with the pit floor. The covering shall consist of a noncombustible material. 1/12/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency Alarm bell does not work on normal or backup power 9/15/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No The car gate switch shall be adjusted to open (and stop the driving machine) when the gate exceeds 2" from the fully closed position. 2/28/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Red Tag) Yes Yes In car emergency phone, alarm bell, and emergency light are inoperable 3/8/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Alarm Bell and Emergency Light do not work when on backup power 5/11/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Alarm bell does not work on normal or backup power 3/28/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency Alarm bell does not work on normal or backup power 2/27/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency Alarm bell does not work on normal or backup power 7/8/2024
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No The in car emergency lighting shall be operational. 2/28/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 2/28/2022