Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No 2021&2022VIO: H(4)/2.5/8.11.2.1.2(e). Non-elevator related items shall not be stored in Machine Room. 12/22/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No 2021&2022VIO: H(2) Machine room door shall be self-closing and self-locking. Closer broken 12/22/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No 2021&2022VIO: G(1)/A17.1-2016:8.6.1.2.1(a)/2.40 Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly 12/22/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No 2021&2022VIO: I(6) Pit light fixture broken and hanging off wall. 12/22/2022
MO Minimum : Elevators (I) - Pits (I)1 No No Clean Pit. 12/22/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light fixture broken and hanging off wall. 1/5/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) Yes No Phase 2 Keyswitch does not work. repair or replace. (REINSPECTION ReQUIRED) 6/10/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.11.2.1.2(e) (Re-Inspection) No No H-4 Mo Min non elevator items stored in machine room 6/10/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No needs current certificate posted 12/22/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.11.2.1.2(e) (Re-Inspection) No No non elevator otems in the machine room 6/10/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No 2-way communication device shall give proper location message, unresponsive on battery power (REINSPECTION REQUIRED) 6/10/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No MCP shall be kept in equipment room, including Oil loss log and Fire service testing log, recorded monthly. 1/5/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No : Emergency/auxiliary lighting shall work with power loss. (REINSPECTION REQUIRED) 6/10/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No 2-way communication device shall give proper location message, unresponsive on battery power (REINSPECTION REQUIRED) 6/10/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Yes No Phase 2 Keyswitch does not work. repair or replace. (REINSPECTION ReQUIRED) 6/10/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No : Emergency/auxiliary lighting shall work with power loss. (REINSPECTION REQUIRED) 6/10/2022