Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Battery lowering device does not work per code. Where auxiliary power lowering operation is installed or altered, it shall conform to 3.26.10. 12/8/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Auxiliary power lowering does not work. Take corrective action and re-test. (2nd Notice)
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Auxiliary power lowering does not work. Take corrective action and re-test. 1/14/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key.
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-closing.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Up to date operating certificate required in the machine room.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Fireman's key switch needs to be replaced. 1/14/2025
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Fireman's key switch needs to be replaced. (2nd Notice)
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Phase 1 & 2 key switches worked intermittently. Could not perform test properly. Take corrective action and perform a successful fire service test. 12/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Install a code data plate. It shall read: Missouri Minimums.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Missing handrail inside car.