Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 7.5 - Lighting 8.6.11.6.2(i) No No The demarcation light fixture failed to illuminate and shall be repaired/replaced. 3/18/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.19 - Maintenance records 8.6.1.4 No No Provide written maintenance records to be kept on site. 3/18/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.19 - Maintenance records 8.6.1.4 No No Provide MCP 3/18/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.5 - Lighting 8.10.4.1.1(e) No No Upper and lower demarcation lights do not work. 3/18/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 8.6.8.13 No No Pits need cleaning. 3/18/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.13 - Handrail systems and safety devices 6.1.3.4 No No Right handrail is cracked, needs to be replaced
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.5 - Lighting 8.6.11.5(i) Demarcation Lighting (Re-Inspect) Yes No Demarcation lights are not working. 8/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.2 - Stop switch 8.10.4.1.2(b) Yes No Lower emergency stop switch cover is broken. 9/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.7 - Combplate and comb step impact device 8.11.4.1(g) Yes No Provide comb impact testing on upper and lower ends 4/5/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.10 - Operating and safety devices 6.1.6.3.1 Emergency Stop Buttons (Re-Inspection) Yes No The plastic cover for the stop switch is missing and shall be reinstalled to prevent accidental activation by passengers. 3/18/2026