Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.10 - Operating and safety devices 6.1.6.3.1 Emergency Stop Buttons (Re-Inspection) x The plastic cover for the stop switch is missing and shall be reinstalled to prevent accidental activation by passengers.
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.5 - Lighting 8.10.4.1.1(e) Upper and lower demarcation lights do not work.
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.2 - Stop switch 8.10.4.1.2(b) x Lower emergency stop switch cover is broken. 9/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.7 - Combplate and comb step impact device 8.11.4.1(g) x Provide comb impact testing on upper and lower ends 4/5/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.19 - Maintenance records 8.6.1.4 Provide written maintenance records to be kept on site.
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.19 - Maintenance records 8.6.1.4 Provide MCP
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.5 - Lighting 8.6.11.5(i) Demarcation Lighting (Re-Inspect) x Demarcation lights are not working. 8/19/2021
A17.1-2016 : Elevators 7.5 - Lighting 8.6.11.6.2(i) The demarcation light fixture failed to illuminate and shall be repaired/replaced.
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 8.6.8.13 Pits need cleaning.