Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a No No Top of car inspection station does not function. 10/9/2018
conversion conversion n/a No No Repair pit light. Pit light not working and electrical wires are exposed. 10/9/2018
conversion conversion n/a No No elevator phone does not function. 10/9/2018
conversion conversion n/a No No Enclose wires from hoistway duct to first floor hall button fixture in metal conduit. 10/9/2018
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Test and log firefighter operation monthly 1/6/2021
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Post firefighter instructions inside the elevator 1/6/2021
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)5 No No Need to install car platform toe guard on elevator. 11/23/2019
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Need to install light switch that operates pit light. Switch should be accessible from the pit access door. 10/9/2018
MO Minimum : Elevators (F) - Electrical Switches (F)6 Yes No THE UPPER DIRECTIONAL SWITCH ARM HAS BEEN REMOVED MAKING THE SWITCH INOPERABLE 4/9/2025
MO Minimum : Elevators (F) - Electrical Switches (F)6 Yes No PHASE 1 FIRE SERVICE SWITCH DOES NOT WORK 4/9/2025
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)6 No No CAR DOES NOT HAVE A CAPACITY / LOADING CLASS / AND ''NO PASSENGERS'' SIGNAGE 5/5/2025
MO Minimum : Elevators (A) - Hoistways (A)16 No No Multicable wiring from hoistway duct to first floor hall button fixture needs to be in flexible metal conduit, not plastic tubing. 10/9/2018