MO Minimum : Elevators (C) - Car Enclosure: Freight (C)6 CAR DOES NOT HAVE A CAPACITY / LOADING CLASS / AND ''NO PASSENGERS'' SIGNAGE
MO Minimum : Elevators (F) - Electrical Switches (F)6 x THE UPPER DIRECTIONAL SWITCH ARM HAS BEEN REMOVED MAKING THE SWITCH INOPERABLE
MO Minimum : Elevators (F) - Electrical Switches (F)6 x PHASE 1 FIRE SERVICE SWITCH DOES NOT WORK
conversion conversion n/a Top of car inspection station does not function. 10/9/2018
conversion conversion n/a Repair pit light. Pit light not working and electrical wires are exposed. 10/9/2018
conversion conversion n/a elevator phone does not function. 10/9/2018
conversion conversion n/a Enclose wires from hoistway duct to first floor hall button fixture in metal conduit. 10/9/2018
MO Minimum : Elevators (A) - Hoistways (A)16 Multicable wiring from hoistway duct to first floor hall button fixture needs to be in flexible metal conduit, not plastic tubing. 10/9/2018
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Need to install light switch that operates pit light. Switch should be accessible from the pit access door. 10/9/2018
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)5 Need to install car platform toe guard on elevator. 11/23/2019
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test and log firefighter operation monthly 1/6/2021
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post firefighter instructions inside the elevator 1/6/2021