Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unintended test procedures do not appear proper for this controller. Re-inspection required 9/1/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unintended test procedures do not appear proper for this controller, still unable to perform unintended movement testing. Re-inspection required 9/5/2023
MO Minimum : Elevators (I) - Pits (I)1 I.1 - The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry. 10/9/2025
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting Need to install machine area lighting to provide 19 ft candles of illumination with the switch adjacent to and accessible from the top floor door 10/9/2025
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting Provide 19 foot candles of illumination measured at the floor in the control space 10/9/2025
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting Need to install machine area lighting to provide 19 foot candles of illumination with the switch adjacent to & accessible from the top floor door. 10/9/2025
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting Need to provide 19 foot candles of illumination measured at the floor in the control space 10/9/2025
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting Install machine area lighting to provide 19 foot candles of illumination with the switch adjacent to & accessible from the top floor door 10/9/2025
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting Provide 19 foot candles of illumination measured at the floor in the control space 10/9/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current state operating certificate shall be displayed in elevator machine room. 10/9/2025