A17.1-1996 : Elevators
|
2.27 - Rope fastenings
|
212
|
|
|
Wedge rope socket is anchored incorrectly. When the steel wire rope has been seated in the wedge socket by the load on the rope, the wedge shall be visible, and at least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope. The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip.
|
3/12/2026
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Up-to-date fire extinguisher is required in the machine room.
|
3/12/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The governor rope and suspension ropes shall have data tags installed.
|
3/11/2021
|
|
A17.1-1996 : Elevators
|
2.11 - Disconnecting Means and Control
|
210.4
|
|
|
The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device.
|
3/12/2026
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
Sump pump discharge hose/piping is leaking water back into the pit. Shall be repaired for proper operation.
|
3/26/2026
|
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
102.1
|
|
|
Remove abandoned light and wiring at the top of the hoistway.
|
3/12/2026
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
Pit shall be cleaned
|
3/26/2026
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Pit light does not work.
|
3/12/2026
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Light bulbs and tubes within the car shall be equipped with guards, be recessed, or be mounted above a drop ceiling to prevent accidental breakage.
|
3/12/2026
|
|
A17.1-1996 : Elevators
|
2.14 - Code data plate
|
215
|
|
|
Install a code data plate. It shall read "A17.1-1996".
|
3/12/2026
|
|
conversion
|
conversion
|
n/a
|
|
|
Finish 5 year test - Reinspection Required
|
3/11/2021
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
|
3/29/2022
|
|
A17.1-1996 : Elevators
|
1.10 - Power opening of doors or gates
|
111.12
|
|
|
Door Restrictor has been removed. Shall be reinstalled and repaired so doors open less than 4" when away from the landings.
|
3/26/2026
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
Clean the pit of oil, dirt, and debris.
|
3/12/2026
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2c (Clean Car Tops)
|
|
|
Car top needs cleaned
|
3/26/2026
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Car Lighting glass tubes shall be protected or reinstall missing drop ceiling.
|
3/26/2026
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
|
3/11/2021
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
3/29/2022
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
3/11/2021
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
3/29/2022
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
3/11/2021
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1002.2f
|
x
|
|
The phase 2 key switch is the wrong hand, this shall be corrected. The switch shall be rotated clockwise to go from the "OFF" to "HOLD" to "ON" position.
|
3/29/2022
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1002.2f
|
x
|
|
The phase 2 key switch is the wrong hand, this shall be corrected. The switch shall be rotated clockwise to go from the "OFF" to "HOLD" to "ON" position.
|
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car ADA telephone shall be operational.
|
11/25/2020
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car ADA telephone shall be operational.
|
10/27/2020
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The category 5 test shall be completed. The following testing items remain: 1. The car buffer shall be tested with rated capacity at rated speed. 2. The counterweight buffer shall be tested at the rated speed.
|
11/25/2020
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Diameter loss due to rouging exceeds proposed criteria. Need to replace suspension means A17.2.3.23 within 90 days.
|
2/5/2019
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
A category 5 test is overdue. The last category 5 test was performed in 2012. A category 5 test shall be scheduled and performed.
|
10/27/2020
|