Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/11/2021
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 3/11/2021
conversion conversion n/a Finish 5 year test - Reinspection Required 3/11/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The governor rope and suspension ropes shall have data tags installed. 3/11/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 3/29/2022
A17.1-1996 : Elevators 2.14 - Code data plate 215 Install a code data plate. It shall read "A17.1-1996".
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device.
A17.1-1996 : Elevators 2.27 - Rope fastenings 212 Wedge rope socket is anchored incorrectly. When the steel wire rope has been seated in the wedge socket by the load on the rope, the wedge shall be visible, and at least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope. The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip.
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Light bulbs and tubes within the car shall be equipped with guards, be recessed, or be mounted above a drop ceiling to prevent accidental breakage.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Clean the pit of oil, dirt, and debris.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Pit light does not work.
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 Remove abandoned light and wiring at the top of the hoistway.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Up-to-date fire extinguisher is required in the machine room.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/11/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/29/2022
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. 3/29/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x The phase 2 key switch is the wrong hand, this shall be corrected. The switch shall be rotated clockwise to go from the "OFF" to "HOLD" to "ON" position. 3/29/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The category 5 test shall be completed. The following testing items remain: 1. The car buffer shall be tested with rated capacity at rated speed. 2. The counterweight buffer shall be tested at the rated speed. 11/25/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car ADA telephone shall be operational. 11/25/2020
conversion conversion conversion - reinspect x Diameter loss due to rouging exceeds proposed criteria. Need to replace suspension means A17.2.3.23 within 90 days. 2/5/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car ADA telephone shall be operational. 10/27/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x A category 5 test is overdue. The last category 5 test was performed in 2012. A category 5 test shall be scheduled and performed. 10/27/2020