MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher in the machine room shall be serviced, there is no service tag that indicates when it was serviced.
|
12/2/2025
|
|
A17.1-1996 : Elevators
|
1.7 - Car door or gate
|
1001.2(a)(7)
|
|
|
Auxiliary battering lowering inoperable, repair & retest
|
12/2/2025
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
110.27 Guarding of live Parts NFPA 72
|
|
|
Provide guards on bulbs in machine room to prevent accidental contact/breakage.
|
1/4/2021
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Remove all non-elevator items from elevator machine room.
|
1/4/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
x
|
|
Auxiliary battery lowering device (emergency rescue unit) does not work. Also, the auxiliary contacts are missing from inside the mainline disconnect switch. The auxiliary contacts are needed to prevent the elevator mainline disconnect from activating the auxiliary lowering device during maintenance and repair visits. Re-inspection required mainline disconnect switch
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
x
|
|
Auxiliary battery lowering inoperable, needs repair. Re-inspection required. This has been noted on the past 2 annual inspection reports.
|
10/28/2024
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Emergency light, bell and phone shall work.
|
7/31/2018
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Auxiliary battery lowering inoperable, needs repair. Re-inspection required
|
11/30/2023
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is inoperable. Re-inspection required
|
11/30/2023
|