Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.7 - Car door or gate 1001.2(a)(7) Auxiliary battering lowering inoperable, repair & retest
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Auxiliary battery lowering inoperable, needs repair. Re-inspection required 11/30/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x Auxiliary battery lowering inoperable, needs repair. Re-inspection required. This has been noted on the past 2 annual inspection reports. 10/28/2024
conversion conversion conversion - reinspect x Emergency light, bell and phone shall work. 7/31/2018
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone is inoperable. Re-inspection required 11/30/2023
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 110.27 Guarding of live Parts NFPA 72 Provide guards on bulbs in machine room to prevent accidental contact/breakage. 1/4/2021
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) Remove all non-elevator items from elevator machine room. 1/4/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The fire extinguisher in the machine room shall be serviced, there is no service tag that indicates when it was serviced.