Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room. 4/16/2021
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 4/16/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/16/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Elevator is equipped with an overspeed valve. The valve is sealed but not tagged. Based on the installation date of 2004, a category 5 test is due on the overspeed valve in 2024. 11/17/2023