A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Items and materials not related to the operation or maintenance of the elevator shall not be stored in the elevator machine room.
|
1/6/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
1/26/2021
|
A17.1-1996 : Elevators
|
4.5 - Access to Hoistway
|
1001.2(d)(5)
|
|
|
The hoistway access switch on the top floor shall be operational.
|
1/6/2022
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
Provide legible Phase 2 fire service operating instructions on the car operating panel (COP).
|
1/6/2022
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide a code compliant MCP including on-site documents.
|
1/6/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The category 1 relief pressure test shall be performed.
|
1/26/2021
|