Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) Items and materials not related to the operation or maintenance of the elevator shall not be stored in the elevator machine room. 1/6/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide a code compliant MCP including on-site documents. 1/6/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Provide legible Phase 2 fire service operating instructions on the car operating panel (COP). 1/6/2022
A17.1-1996 : Elevators 4.5 - Access to Hoistway 1001.2(d)(5) The hoistway access switch on the top floor shall be operational. 1/6/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The category 1 relief pressure test shall be performed. 1/26/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 1/26/2021