Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.27 - Rope fastenings 1001.2(b)(25) The dead end hitch has a spring that is broken in the machine room that shall be replaced for the hoisting ropes to have an equal amount of tension. 7/16/2020
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. 10/20/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The elevator drive sheave insert has degraded to the point of replacement of the insert is required. The elevator has been removed from service by the maintenance provider until the sheave insert is replaced. 7/19/2023