Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No :Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly.
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Non-elevator related items shall not be stored in Machine Room.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door shall be self-closing and self-locking
MO Minimum : Elevators (I) - Pits (I)1 No No Pit shall be kept dry, water/oil in pit. Clean pit, inspect pit equipment , remove rust and paint equipment as needed. Investigate/repair water leak.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Provide mcp in machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No needs current certificate posted in frame in machine room 10/13/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No No frame present 8/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired 2015) 8/5/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No S(1)/6.5.9.3/8.11.2.2.6. Fire service Door Open (Momentary/Peekaboo) shall work properly. (REINSPECTION REQUIRED) 8/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Travel Cable insulation cracked in multiple places, exposing internal wiring. Should be replaced. 8/5/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No S(1)/6.5.9.3/8.11.2.2.6. Fire service Door Open (Momentary/Peekaboo) shall work properly. (REINSPECTION REQUIRED) 8/5/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No No frame present 8/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired 2015) 8/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Travel Cable insulation cracked in multiple places, exposing internal wiring. Should be replaced. 8/5/2021