MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Travel Cable insulation cracked in multiple places, exposing internal wiring. Should be replaced.
|
8/5/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Travel Cable insulation cracked in multiple places, exposing internal wiring. Should be replaced.
|
8/5/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door shall be self-closing and self-locking
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Non-elevator related items shall not be stored in Machine Room.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept dry, water/oil in pit. Clean pit, inspect pit equipment , remove rust and paint equipment as needed. Investigate/repair water leak.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
needs current certificate posted in frame in machine room
|
10/13/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
No frame present
|
8/5/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
No frame present
|
8/5/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
S(1)/6.5.9.3/8.11.2.2.6. Fire service Door Open (Momentary/Peekaboo) shall work properly. (REINSPECTION REQUIRED)
|
8/5/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
S(1)/6.5.9.3/8.11.2.2.6. Fire service Door Open (Momentary/Peekaboo) shall work properly. (REINSPECTION REQUIRED)
|
8/5/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
:Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide mcp in machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired 2015)
|
8/5/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired 2015)
|
8/5/2021
|