A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV would not set, Re-inspect when repaired or replaced
|
4/4/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Scavenger pumps that do not record the amount of oil returned to the hydraulic tank can not be installed in the elevator pit. Either install a recordable pump or limit the amount of oil stored in the pit to 5 gallons.
|
3/17/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
Overspeed valve is not sealed and needs full load test & tripping speed checked, Re-inspect by 2/9/22
|
3/17/2022
|