Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) Yes No OSV would not set, Re-inspect when repaired or replaced 4/4/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Scavenger pumps that do not record the amount of oil returned to the hydraulic tank can not be installed in the elevator pit. Either install a recordable pump or limit the amount of oil stored in the pit to 5 gallons. 3/17/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No Overspeed valve is not sealed and needs full load test & tripping speed checked, Re-inspect by 2/9/22 3/17/2022