A17.1-1996 : Elevators
|
3.10 - Hoistway construction
|
100
|
No
|
No
|
Repair the roof leak over the hoistway , then repair the drywall back to the fire rating of 1 hour.
|
10/19/2020
|
|
A17.1-1996 : Elevators
|
4.8 - Hoistway enclosure
|
100.1
|
No
|
No
|
Patch the holes drilled in the machine room wall below the main line disconnect box.
|
6/8/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
No
|
No
|
Repack the leaking left jack. excessive amt. 5 gal overflowed.
|
10/19/2020
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
No
|
No
|
Remove the added Freon lines from the elevator machine room
|
10/19/2020
|