MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
5/26/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be displayed in the elevator machine room.
|
5/26/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
5/26/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Water and oil shall not be allowed to accumulate on pit floors. Note: The pit has at least 12" of water in it.
|
10/12/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Could not get elevator to revert back to normal operation from fire service operation. Take corrective action as needed.
|
12/29/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be displayed in the elevator machine room.
|
12/5/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit has around 14" of water in it. The pit shall be kept clean and dry and water and oil shall not be allowed to accumulate on pit floors.
|
12/5/2024
|