MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time, the elevator was out of service for repair. The a full category 5 test shall be performed before the inspection is completed.
|
9/6/2022
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
There are two car door restrictor brackets missing on the 2nd floor door and fascia. The car door restrictor brackets shall be reinstalled so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required.
|
9/11/2019
|
A17.1-1996 : Elevators
|
5.10 - Compensating chains, ropes, and sheaves
|
1001.2(e)(8)
|
x
|
|
The weight compensation chain roller guide is the counterweight before the counterweight buffer is fully compressed. Readjust the weight compensation chain roller guide to allow the buffer to fully compress.
|
9/11/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11
|
x
|
|
Counterweight runby shall be code compliant.
|
|