Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Recovery pump in the elevator pit not allowed per memo from the state, memo 006 A17.1 8.6.5.5
MO Minimum : Elevators (H) - Machine Rooms (H)4 Repair/replace vic coupling in the machine room that is leaking all over the floor
A17.1-2016 : Elevators 3.11 - Hoistway smoke control 3.1 Smoke damper at the top of the hoistway should be closed and only open when the hoistway smoke detectors are activated (2.1.4)
MO Minimum : Elevators (I) - Pits (I)1 Clean the pit, pile of rags should not be left in the pit
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service test and post a log in the machine room 7/21/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x replace emergency light battery, it is dead 4/1/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 7/14/2021
MO Minimum : Elevators (H) - Machine Rooms (H)4 do not store non-elevator related material in the machine room (toilet snake) 7/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x replace the emergency light battery, it is dead 8/17/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates replace the fire service phase 1 keyswitch collar, can not read markings on the collar 5/31/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the state operating certificate in the machine room is to be updated every year 5/31/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements smoke damper at the top of the hoistway is open, it should be closed and only open when smoke detector is activated or when the motor fails 5/31/2022
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 recovery pump in the elevator pit is not allowed per state of Missouri memo 006, replace with bucket 10/26/2023
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) replace burnt out machine room light bulbs 10/26/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 replace vic coupling in the machine room that is leaking all over the machine room floor 10/26/2023
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.11.3.1.1(r) x Door restrictor has been disabled, repair and adjust the door restrictor 11/4/2024