A17.1-2016 : Elevators
|
3.11 - Hoistway smoke control
|
3.1
|
|
|
Smoke damper at the top of the hoistway should be closed and only open when the hoistway smoke detectors are activated (2.1.4)
|
|
A17.1-2016 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
8.11.3.1.1(r)
|
x
|
|
Door restrictor has been disabled, repair and adjust the door restrictor
|
11/4/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean the pit, pile of rags should not be left in the pit
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service test and post a log in the machine room
|
7/21/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
replace emergency light battery, it is dead
|
4/1/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
|
7/14/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
replace the emergency light battery, it is dead
|
8/17/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
do not store non-elevator related material in the machine room (toilet snake)
|
7/14/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
replace the fire service phase 1 keyswitch collar, can not read markings on the collar
|
5/31/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the state operating certificate in the machine room is to be updated every year
|
5/31/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
smoke damper at the top of the hoistway is open, it should be closed and only open when smoke detector is activated or when the motor fails
|
5/31/2022
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
recovery pump in the elevator pit is not allowed per state of Missouri memo 006, replace with bucket
|
10/26/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
replace burnt out machine room light bulbs
|
10/26/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
replace vic coupling in the machine room that is leaking all over the machine room floor
|
10/26/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Recovery pump in the elevator pit not allowed per memo from the state, memo 006 A17.1 8.6.5.5
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Repair/replace vic coupling in the machine room that is leaking all over the floor
|
|