Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect Yes No Governor and safeties shall be tested. 5/22/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No The safeties pulled out 60" for the annual test. The drum operated safety rope shall pull out a maximum of 42" before the safeties contact the rail 3/3/2021
conversion conversion n/a No No Need copy of current state operating certificate in machine room. 6/13/2023
conversion conversion n/a No No Door closing force exceeds 30 lbs. 6/13/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 6/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Remove all material, including 4 cinder blacks from the car top. 6/13/2023
MO Minimum : Elevators (A) - Hoistways (A)16 No No Install a cover on the door operator. 6/13/2023
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) No No Install a suspension rope and governor rope data tag. 6/13/2023
MO Minimum : Elevators (A) - Hoistways (A)16 No No Remove unsupported wiring from the overhead. 6/13/2023
MO Minimum : Elevators (A) - Hoistways (A)13 No No The holes in the overhead shall be sealed with approved solid material. 6/13/2023
MO Minimum : Elevators (A) - Hoistways (A)16 No No The open electrical box with exposed wiring in the hoistway at the 4th floor shall be covered. 6/13/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No The material not necessary for the operation of the elevator, trash, and defective parts shall be removed from the machine room. 6/13/2023
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No The covers shall be installed on all electrical equipment in the machine room, including the controllers. 6/13/2023
MO Minimum : Elevators (H) - Machine Rooms (H)6 No No The machines shall be numbered. 6/13/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No A monthly fire service testing log shall be posted and kept on-site. 6/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A maintenance control program (MCP) shall be provided. 6/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams No No An up to date, legible copy of the schematics shall be located in the machine room for each elevator. 6/13/2023
MO Minimum : Elevators (H) - Machine Rooms (H)7 No No Wiring running from controller 1 to controller 2 shall be enclosed in raceway or wireway. 6/13/2023
MO Minimum : Elevators (J) - Counterweights (J)2 No No Suspension ropes on counterweight shackles shall have all cotter pins installed. 6/13/2023
MO Minimum : Elevators (A) - Hoistways (A)16 No No Traveling cables shall be properly supported and run in wireway or raceway 6' past the point of suspension in the hoistway. 6/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No A current ABC type fire extinguisher shall be located in the machine room. 6/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No The car top shall be kept clean. Clean the car top. 6/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The in car emergency bell shall be operational. 3/28/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The in car emergency lighting shall be operational. 3/28/2024