MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
6/13/2023
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
The holes in the overhead shall be sealed with approved solid material.
|
6/13/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
The material not necessary for the operation of the elevator, trash, and defective parts shall be removed from the machine room.
|
6/13/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
The covers shall be installed on all electrical equipment in the machine room, including the controllers.
|
6/13/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)6
|
|
|
The machines shall be numbered.
|
6/13/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
A monthly fire service testing log shall be posted and kept on-site.
|
6/13/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A maintenance control program (MCP) shall be provided.
|
6/13/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
|
|
Wiring running from controller 1 to controller 2 shall be enclosed in raceway or wireway.
|
6/13/2023
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Holes in the hoistway between floors 1 and 2 shall be sealed with approved solid materials.
|
6/13/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams
|
|
|
An up to date, legible copy of the schematics shall be located in the machine room for each elevator.
|
6/13/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current ABC type fire extinguisher shall be located in the machine room.
|
6/13/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
The car top shall be kept clean. Clean the car top.
|
6/13/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept clean. Clean the pit.
|
6/13/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Door close button does not work on Phase II fire service.
|
3/8/2022
|
conversion
|
conversion
|
conversion - red tag
|
x
|
x
|
Governor jaws and rope shall be replaced, car safeties would not set.
|
4/15/2019
|
conversion
|
conversion
|
conversion - red tag
|
x
|
x
|
Cable on wind up drum is damaged and shall be replaced.
|
4/15/2019
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
Governor jaws and governor rope shall be replaced, car safeties would not set.
|
5/22/2020
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
Cable on wind up drum is damaged and shall be replaced.
|
5/22/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
The door close button shall be operational on firefighters Phase 2 operation. (Doors presently close with car call button, but not with door close button) - The installation year and adopted code at time of installation shall be confirmed to determine if this violation applies.
|
3/3/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The emergency lighting shall be operational.
|
3/3/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The alarm bell shall be operational on main and auxiliary power.
|
3/3/2021
|