Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 x Counterweight runby shall be code compliant.
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)8 x x Cannot turn car over for use until safeties are repaired. 5/28/2019