Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.3.1.5(a) There is water and oil that has accumulated in the pit. Remove the oil and water from the pit and correct source of leaks. The pit shall be kept dry.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State Operating Certificate is required in the machine room.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 The oil log and fire service log shall be recorded monthly. They are not being updated.
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering shall be operational. Note: Not corrected at time of 8/26/24 re-inspection.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Heat detector shall be within 24" of sprinkler head in the machine room. Note: Not corrected at time of 8/26/24 re-inspection.
A17.1-2016 : Elevators 1.17 - Standby power operation 3.26.10 Auxiliary power lowering device shall be operational. 10/5/2020
A17.1-2016 : Elevators 1.17 - Standby power operation 3.26.10 x Auxiliary power lowering device is still not operational. Repair as needed. 6/1/2021
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Emergency/standby power operation of the elevator shall be tested to complete the annual inspection. 4/26/2022
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering device is not operating properly. 4/1/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering device is not operating properly. Note: Display reads LODC 7/8/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 8/26/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering shall be operational. 8/26/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Heat detector shall be within 24" of sprinkler head in the machine room. 8/26/2024