Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Heat detector shall be within 24" of the sprinkler head.
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering device is not operating properly. 6/15/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering device is not operating properly. (2nd Notice) 7/8/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering shall be operational.
A17.1-2016 : Elevators 1.17 - Standby power operation 3.26.10 x Auxiliary power lowering device is still not operational. Repair as needed. 6/1/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 3.26.10 Auxiliary power lowering device shall be operational. 10/5/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the machine room.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.3.1.5(a) There is water and oil that has accumulated in the pit. Remove the oil and water from the pit and correct source of leaks. The pit shall be kept dry.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 The fire service monthly testing log and oil log are not being completed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Replace the faded and unreadable in-car Phase 2 fire service instructions.