Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. 5/19/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 MCP, including PM records and monthly fire service test log, are not being properly documented. 12/15/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. Note: The phone dials out but two way communication couldn't be established. 12/19/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work properly. Getting the error message "call cannot be completed as dialed", and volume is extremely low. 11/20/2023