Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unit broke during inspection - The safeties shall be tested as part of a category 5 test. 10/13/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service shall be tested. 10/13/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be displayed in the elevator machine room. 6/16/2022
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Fire Extinguisher is out of date. 8/12/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The elevator went down during the inspection. The car is stuck on the safeties. Elevator left out of service by elevator maintenance company. 9/18/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unable to complete inspection due to unit getting stuck on safeties. The following testing items still need to be performed and witnessed to complete the annual inspection. Remaining testing items: Set safeties again, test fire service, testing of governor, testing of car & counterweight buffers, and scan of the hoistway. 9/18/2023