Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Inspection incomplete due to rated speed being listed at 200 FPM, but the elevator is only running at 125 FPM. The weight portion of the 5-year test shall be completed.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Unit broke during inspection - The safeties shall be tested as part of a category 5 test. 10/13/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Fire service shall be tested. 10/13/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be displayed in the elevator machine room. 6/16/2022
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No No Fire Extinguisher is out of date. 8/12/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No The elevator went down during the inspection. The car is stuck on the safeties. Elevator left out of service by elevator maintenance company. 9/18/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Unable to complete inspection due to unit getting stuck on safeties. The following testing items still need to be performed and witnessed to complete the annual inspection. Remaining testing items: Set safeties again, test fire service, testing of governor, testing of car & counterweight buffers, and scan of the hoistway. 9/18/2023