A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be displayed in the elevator machine room.
|
6/16/2022
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
No
|
No
|
Fire Extinguisher is out of date.
|
8/12/2022
|
|
A17.1-1996 : Elevators
|
1.3 - Operating control devices
|
210.1a
|
No
|
No
|
Operating Control Devices: Phone button and phone symbol damaged in COP, currently being held in place by tape.
|
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
2-WAY COMMUNICATION DEVICE SHALL WORK.
|
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1002.2g (Standby Power Operation)
|
Yes
|
No
|
Emergency Battery Power/Rescue system shall be tested and operation verified.
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Unit broke during inspection - The safeties shall be tested as part of a category 5 test.
|
10/13/2020
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Fire service shall be tested.
|
10/13/2020
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
Yes
|
No
|
The elevator went down during the inspection. The car is stuck on the safeties. Elevator left out of service by elevator maintenance company.
|
9/18/2023
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Unable to complete inspection due to unit getting stuck on safeties. The following testing items still need to be performed and witnessed to complete the annual inspection. Remaining testing items: Set safeties again, test fire service, testing of governor, testing of car & counterweight buffers, and scan of the hoistway.
|
9/18/2023
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Inspection incomplete due to rated speed being listed at 200 FPM, but the elevator is only running at 125 FPM. The weight portion of the 5-year test shall be completed.
|
8/25/2026
|
|
A17.1-1996 : Elevators
|
3.20 - Governor rope
|
206.5 Governor Ropes
|
Yes
|
Yes
|
Governor rope is frayed and shall be replaced. Unit out of service until replaced and reinspected.
|
|