A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be displayed in the elevator machine room.
|
6/16/2022
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Fire Extinguisher is out of date.
|
8/12/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The elevator went down during the inspection. The car is stuck on the safeties. Elevator left out of service by elevator maintenance company.
|
9/18/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Unable to complete inspection due to unit getting stuck on safeties. The following testing items still need to be performed and witnessed to complete the annual inspection. Remaining testing items: Set safeties again, test fire service, testing of governor, testing of car & counterweight buffers, and scan of the hoistway.
|
9/18/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Unit broke during inspection - The safeties shall be tested as part of a category 5 test.
|
10/13/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fire service shall be tested.
|
10/13/2020
|