Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No 3rd floor electronic directional arrow missing cover, provide.
A17.1-1996 : Elevators 1.3 - Operating control devices 1001.2(a)(3) No No A key switch on the car operating panel in the car is pushed in resulting in a possible electrical hazard and shall be repaired. 11/15/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean car top.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) Yes No Clean the pit 6/5/2024
MO Minimum : Elevators (I) - Pits (I)1 Yes No Clean the pit.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) No No Clean the pit. 11/15/2025
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f Yes No Door open function failed on Phase II. 6/5/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Hole in COP, missing switch. Seal. Potential life/limb hazard.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Key switch halo ring is worn and unreadable.
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) Yes No OSV in the pit is unsealed, provide testing. 4/19/2024
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) Yes No OSV in the pit is unsealed. Provide testing. 6/5/2024
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Yes No Phase I halo worn and unreadable, replace.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Yes No Post current State Elevator Certificate. 6/5/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 11/15/2025
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures No No Post Phase I instructions near f/f switch in the lobby. 11/15/2025
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Yes No Post Phase I instructions. 6/5/2024
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Yes No Post Phase I instructions.
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(5) Oil Leakage Collection No No Provide code compliant means of oil recovery in the pit (buckets) 11/15/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Yes No Provide code compliant means to collect jack oil for each piston. 6/5/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Provide existing battery backup lowering unit to work correctly. 4/19/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) Yes No Provide existing battery backup lowering unit to work. 6/5/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Provide existing battery backup lowering unit to work.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Provide existing phone to work.
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d No No Provide machine room door to be self locking (no button)
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(5) Oil Leakage Collection Yes No Provide means to collect oil from each piston.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Provide Phase I halo ring to be readable, worn.
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(5) Oil Leakage Collection No No Remove scavenger oil lines going back to the tank. 11/15/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Yes No Remove scavenger return line. 6/5/2024
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(5) Oil Leakage Collection Yes No Remove scavenger unit from pit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Yes No Remove scavenger unit from the pit. 6/5/2024
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(5) Oil Leakage Collection No No Remove scavenger unit from the pit. 11/15/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)1 Yes No Replace missing car hand rails.
A17.1-1996 : Elevators 1.12 - Car enclosure 204 Yes No Replace missing car hand rails. 6/5/2024
A17.1-1996 : Elevators 1.12 - Car enclosure 204 No No Replace missing car handrails. 11/15/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Seal hole in the car operating panel, potential life/limb hazard. 11/15/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No There is a oil recovery unit installed in the pit of this elevator designed to return the oil leakage from the packing gland on the cylinder head. The State of Missouri has determined that this device does not suffice for oil leakage and is only allowed for temporary use until the packing gland can be repaired/replaced. Remove the recovery unit after the packing gland has been repaired/replaced and record the oil loss per A17.1 2016 - 8.6.5.5.7 11/15/2025
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) Yes No This elevator has an overspeed valve device installed that is not sealed and is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection is required. 7/6/2023