MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Phase 1 switch halo to be replaced (unreadable and not proper color)
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Car top lighting does not work.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
A code compliant MCP and related on-site documentation shall be provided. Note: No oil or fire service log for 2022 or 2023.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current state operating permit shall be displayed.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
Pit shall be kept clean. Remove excess debris.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2b (Clean Machine Room)
|
|
|
Machine room shall be kept clean.
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Evacuation procedures are missing from the MCP.
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2c (Clean Car Tops)
|
|
|
The top of the car shall be kept clean.
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
Fire service testing log is missing from the MCP.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Main c.o.p. alarm bell inoperative on emergency power, repair
|
5/17/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Replace all missing hoistway door sight guards at terminal floors
|
5/17/2019
|
conversion
|
conversion
|
n/a
|
|
|
Clean pit
|
1/15/2020
|
A17.1-1996 : Elevators
|
2.36 - Hydraulic Cylinders
|
1004.2(b)(19)
|
|
|
Repack left cylinder - excessive leaking.
|
1/15/2020
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a
|
x
|
|
Clean pit.
|
2/19/2020
|
A17.1-2016 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
8.11.3.1.2(w)
|
|
|
While conducting pressure test noticed oil shooting back into the tank from the Victaulic fitting in the tank. REINSPECT REQUIRED
|
6/6/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Place current state operating certificate in elevator machine room
|
11/30/2023
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
Replace cylinder gland packing seals.
|
12/5/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean pit.
|
12/5/2023
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
Car door restrictor shall work through-out hoistway
|
9/16/2024
|
A17.1-1996 : Elevators
|
1.7 - Car door or gate
|
204.4
|
x
|
|
Car gate switch (rear) shall not register "closed" at greater than 2" open.
|
9/16/2024
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light (rear) shall work
|
9/16/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell (rear switch) shall work with loss of main 120v power.
|
9/16/2024
|