Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 Replace cylinder gland packing seals. 12/5/2023
MO Minimum : Elevators (I) - Pits (I)1 Clean pit. 12/5/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Place current state operating certificate in elevator machine room 11/30/2023
A17.1-2016 : Elevators 2.35 - Supply Line and Shutoff Valve 8.11.3.1.2(w) While conducting pressure test noticed oil shooting back into the tank from the Victaulic fitting in the tank. REINSPECT REQUIRED 6/6/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Phase 1 switch halo to be replaced (unreadable and not proper color)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Car top lighting does not work.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A code compliant MCP and related on-site documentation shall be provided. Note: No oil or fire service log for 2022 or 2023.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current state operating permit shall be displayed.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Pit shall be kept clean. Remove excess debris.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) Machine room shall be kept clean.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Evacuation procedures are missing from the MCP.
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) The top of the car shall be kept clean.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Fire service testing log is missing from the MCP.
conversion conversion n/a Clean pit 1/15/2020
A17.1-1996 : Elevators 2.36 - Hydraulic Cylinders 1004.2(b)(19) Repack left cylinder - excessive leaking. 1/15/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a x Clean pit. 2/19/2020
conversion conversion conversion - reinspect x Main c.o.p. alarm bell inoperative on emergency power, repair 5/17/2019
conversion conversion conversion - reinspect x Replace all missing hoistway door sight guards at terminal floors 5/17/2019
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Car door restrictor shall work through-out hoistway 9/16/2024
A17.1-1996 : Elevators 1.7 - Car door or gate 204.4 x Car gate switch (rear) shall not register "closed" at greater than 2" open. 9/16/2024
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light (rear) shall work 9/16/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Alarm bell (rear switch) shall work with loss of main 120v power. 9/16/2024