A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
x
|
x
|
Perform monthly fire service test and post test log in the machine room
|
11/2/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
repair the alarm bell, it did not work on normal power or on emergency power
|
11/2/2020
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate in the machine room expired in 2017, update with current state operating certificate when received
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the copy of the state operating certificate in the machine room is to be updated annually
|
1/20/2021
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(j)
|
|
|
the machine room fire extinguisher is to be inspected and tagged annually
|
1/20/2021
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection)
|
|
|
the fire hat symbol is missing on the car operating panel position indicator
|
1/20/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the state operating certificate on display in the elevator machine room expired in 2017, replace with current certificate annually when received from the state
|
|