| A17.1-1996 : Elevators | CSR  40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/18/2020 | 
                
                    | A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) |  |  | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 8/18/2020 | 
                
                    | A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 |  |  | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Rescue plan is missing. (This item is for notification purposes for future violation in 2022) | 9/3/2021 | 
                
                    | A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 |  |  | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Fire service testing must be documented monthly. It has not been documented since 2/2022. |  | 
                
                    | A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.5.7 Record of Oil Usage |  |  | Oil loss log has not been documented since 2014. |  | 
                
                    | A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x |  | In car emergency telephone does not work and shall be repaired and tested. | 2/6/2019 | 
                
                    | A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x |  | Emergency phone shall be operational. | 9/16/2022 | 
                
                    | A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x |  | Battery lowering unit shall be operational. | 9/16/2022 |