Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV needs to have full load tested in 90 days or less. Re-inspection required 11/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 1/10/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Gland Packings and Seals The hydraulic cylinder gland packing is leaking excessively and shall be replaced. 2/20/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 3.18 Remove scavenger line from jack that goes all the way back to tank. Seal fittings as needed. 11/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 Machine room door shall be self locking type. 11/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.32 - Control Valve 8.11.3.1.2 (o) x Car failed 15 min stand test. Determined it to be leaking back through valve. Repair and reinspect. 8/9/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current operating certificate shall be properly displayed in the machine room 1/10/2023