A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
There is no State Operating Certificate in the machine room.
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
The oil log and fire service log are not being updated monthly.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Replace faded in-car capacity plate.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Replace faded in-car phase 2 instruction plate.
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
Battery lowering shall be operational.
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
3.26.10
|
|
|
Auxiliary power lowering device shall be operational.
|
10/5/2020
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test.
|
6/1/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car telephone shall be operational. Note: The person answering the phone cannot hear the person making the call from the elevator.
|
6/15/2023
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it. Note: The MO state certificate is not posted in the machine room as required.
|
6/22/2023
|