Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 6/1/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it. Note: The MO state certificate is not posted in the machine room as required. 6/22/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car telephone shall be operational. Note: The person answering the phone cannot hear the person making the call from the elevator. 6/15/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate There is no State Operating Certificate in the machine room.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 The oil log and fire service log are not being updated monthly.
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering shall be operational.
A17.1-2016 : Elevators 1.17 - Standby power operation 3.26.10 Auxiliary power lowering device shall be operational. 10/5/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Replace faded in-car capacity plate.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Replace faded in-car phase 2 instruction plate.