Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) No No REPLACE DAMAGE OIL MINDERR JUNCTION BOX IN PIT 2/18/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM 2/18/2026
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) Yes No The Auxiliary power lowering shall be functional.
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No REPAIR PHONE IN THE CAR 2/18/2026