Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) REPLACE DAMAGE OIL MINDERR JUNCTION BOX IN PIT
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x Unit has O.S. valve. It is sealed needs a full load os valve test in 2024. If test not done in 30 days unit could be red tagged out of service 4/21/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x REPAIR PHONE IN THE CAR