Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Clean machine room. 9/3/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No current cirt not displayed 2/28/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No HVAC unit in machine room not cooling. 9/6/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No HVAC unit not working in machine room. 9/3/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No mach room door not self locking 1/1/2025
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No mach. room lts not working no lt sw by entrance door 2/28/2023
MO Minimum : Elevators (I) - Pits (I)8 No No need sump pump cover 2/28/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no current cirt displayed 8/28/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no current cirt displayed 1/1/2025
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No no lt sw in machroom for lights to turn lts. on 8/28/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Provide an up to date fire extinguisher in machine room. No tag or date on the one provided. 9/3/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Provide up to date fire extinguisher in machine room. 9/3/2019
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No WATER FROM CONDENSATE LINE TO AC UNIT ON ELEVATOR FOOR 8/20/2025
MO Minimum : Elevators (I) - Pits (I)1 No No Water in pit. 9/3/2019
MO Minimum : Elevators (I) - Pits (I)3 No No Water in pit. Repair sump pump
MO Minimum : Elevators (I) - Pits (I)2 No No water on pit floor 1/1/2025
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors Yes No door restrictor not working rear door 8/16/2023
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 107.1b Yes No runby less than 6 in 7/15/2020
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No emg. phone not working 8/23/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No phone not working had no power 7/7/2022
MO Minimum : Elevators (F) - Electrical Switches (F)2 Yes Yes Bottom directional limit not working. 8/20/2019
MO Minimum : Elevators (F) - Electrical Switches (F)2 Yes Yes Bottom final limit not working properly. It stops the elevator, but gets stuck in the open position. 8/20/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No emg bell an lt not working 7/15/2020